Chapter 2 Parameter Descriptions
Line Rated Voltage
Linear Number: P146
Default Value: 2300V (2.3kV), 2400V (2.4 kV),
3000V (3.0 kV), 3300V (3.3 kV),
4000V (4.0 kV), 4160V (4.16 kV),
6000V (6.0 kV), 6300V (6.3 kV), 6900V (6.9 kV),
10000V (10.0 kV),
11000V (11.0 kV)
Minimum Value: 0V
Maximum Value: 32767V
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter is the input voltage rated value.
Line Rated Frequency
Linear Number: P147
Default Value: 50 Hz
Minimum Value: 0 Hz
Maximum Value: 32767 Hz
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter is the input voltage rated frequency.
Transformer Rated Power
Linear Number: P148
Default Value: 0 kVA
Minimum Value: 0 kVA
Maximum Value: 32767 kVA
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter is the transformer rated power.
Transformer Short Circuit Impedance
Linear Number: P149
Default Value: 5%
Minimum Value: 0%
Maximum Value: 100%
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter is the input transformer short circuit impedance.