90 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 2 Parameter Descriptions
Fan Control Fan Stop Delay
Linear Number: P102
Default Value: 1 min
Minimum Value: 0 min
Maximum Value: 10 min
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the fan stop delay time when the drive is stopping normally.
Fan Control Transformer Cabinet Fan Quantity Upper Limit
Linear Number: P106
Default Value: 10
Minimum Value: 0
Maximum Value: 16
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the upper limit for the Fan Control Transformer Cabinet Fan
Quantity.
Fan Control TX Cabinet Fan Fault Trip Delay
Linear Number: P116
Default Value: 30 min
Minimum Value: 1 min
Maximum Value: 60 min
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the delay trip time when the TX cabinet fan has a fault.
Fan Control Filter Cabinet Fan Fault Trip Delay
Linear Number: P117
Default Value: 30 min
Minimum Value: 1 min
Maximum Value: 60 min
Access Level: Setup, R&D
Read/Write: Read/Write
Modify Level: Online/Offline
This parameter sets the delay trip time when the filter cabinet fan has a fault.