Fault List & Troubleshooting 463
© 2020, ATEÏS. All rights reserved.
Indication:
LED Indicator: When this error is detected, the following LED will light up:
o G. Fault LED on the front panel of the IDA8C/S.
Log:
o "Global AteisNet Broken" message displays on the touch screen of IDA8C.
o A text message displays at the [Machine Fault Record] window in Ateis Studio, see the
picture as below.
A buzzing sound will be outputted to the monitoring speaker on the front panel of the IDA8C.
Troubleshooting:
Check the wire connection between all the IDA8C/S on the Global Ateis Net.
If the wire connection is connected properly, the device must be checked as the following:
For IDA8C:
Prepare a workable IDA8S device, establish the Ateis Net wire connection between the IDA8C
and the IDA8S. Deploy the Ateis Net using Ateis Studio.
If the fault is not solved, please check the hardware version of Ateis Net card.
For each IDA8S on the Ateis Net:
Prepare a workable IDA8C device, establish the Ateis Net wire connection between the IDA8C
and the IDA8S. Deploy the Ateis Net using Ateis Studio and perform the examination as
referred to in the preceding paragraph.
If the fault is not solved, replace the Ateis Net card of the IDA8S.
Once it recovers, the log will show:
"Global AteisNet Normal Mode"
7.1.10 Fireman Error
The Fireman microphone has an error.
Indication:
LED Indicator: When this error is detected, the following LEDs will light up:
o G. Fault LED on the front panel of the IDA8C/S.
Log:
o Fireman Open/Short:
"Fireman Error" or "Fireman Audio Open" display on the touch screen of IDA8C.
o A text message displays at the [Machine Fault Record] window in Ateis Studio, see the
picture as below.
A buzzing sound will be outputted to the monitoring speaker on the front panel of the IDA8C.