Chapter 4: AC Drive Parameters
Page 4–35
DURApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
Type Hex Addr Dec Addr
P0.05 Motor Auto Tune
R/W 0005 40006
Range/Units (Format: 16-bit binary) Default
0: Disable
1: Measure motor in dynamic status (motor spinning)
2: Measure motor in static status (motor not spinning)
0
Measured values will be written to (P0.06: Motor 1 Rs and P0.07: Motor 1 No-Load Current for
motor #1) or (P0.15: Motor 2 Rs and P0.16: Motor 2 No-Load Current for motor #2) automatically by
the GS4 drive.
NO TE: When auto-tuning 2 motors, the user needs to set a multi-function input terminal to
setting 14 for motor selection or change P0.10 for motor 1/motor 2 selection.
NO TE: The rated speed (P0.03) can’t be larger than or equal to 120xF/P; [where F = rated
frequency P0.02 or P0.13; P = number of motor poles P0.09 or P0.18].
Auto-Tuning (Dynamic):
1)
Make sure that the motor wiring is correct�
2)
Make sure that you can start and stop the drive (e�g� using the Run key if in Local Mode, or with
digital inputs if using terminals), and that an E-stop is wired�
3)
Make sure that the parameter values in the table below are correct:
Parameter Motor 1 Motor 2
Maximum Output Voltage P0�00 P0�11
Motor Rated Current P0�01 P0�12
Motor Base Frequency P0�02 P0�13
Motor Rated RPM P0�03 P0�14
Motor Rated Horsepower P0�08 P0�17
Motor Pole Numbers P0�09 P0�18
4)
Before dynamic auto-tuning, make sure the motor output shaft is not connected to a load� If
the motor cannot be separated from the load, static auto-tuning (P0�05=1) is recommended�
5)
Set P0�05=1 to select dynamic auto-tuning� Trigger the Run command; either keypad <RUN>
or external terminals depending on how you have P3�00 and P3�01 configured�
WARNING: Within a few seconds, the motor shaft will begin to turn� An “Auto Tuning” warning
will begin to flash on the keypad display, and will continue until auto tuning is complete� If the
motor has to be stopped during Auto Tuning, an “Auto Tune Error” will be generated� To restart
Auto Tuning, clear the error and restart this procedure again�
6)
When auto-tuning is complete, P0�05 will default back to 0, and Motor1 parameters (P0�06 and
P0�07) and/or Motor2 parameters (P0�15 and P0�16) will be written to the drive�
If the motor is statically auto-tuned (P0�05=2), the GS4 drive will NOT measure no-load current�
It is the responsibility of the user to obtain the motor no-load current value and manually enter
the value in P0�07 for Motor1 and P0�16 for Motor2� Motor no-load current may be available on
the motor nameplate or in the motor manufacturers performance specifications�
Type Hex Addr Dec Addr
P0.06 Motor 1 Resistance
R/W 0006 40007
Range/Units (Format: 16-bit unsigned) Default
0~65.535Ω
0
Motor Auto Detection (P0.05) will set this parameter value. Before using Motor Auto Detection, set
P0.10 to Motor 1. Motor 1 Rs (P0.06) value may be entered manually. If this information is not on
the motor nameplate, consult the manufacturer specifications.

Table of Contents

Other manuals for Automation Direct DURApulse GS4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automation Direct DURApulse GS4 and is the answer not in the manual?

Automation Direct DURApulse GS4 Specifications

General IconGeneral
BrandAutomation Direct
ModelDURApulse GS4
CategoryController
LanguageEnglish

Related product manuals