EasyManua.ls Logo

Automation Direct DURApulse GS4 - Page 195

Automation Direct DURApulse GS4
542 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4: AC Drive Parameters
Page 4–101
DURApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
Type Hex Addr Dec Addr
P4.24 AI V/Hz Calculated Selection
R/W 0418 41049
Range/Units (Format: 16-bit binary) Default
0: All Inputs Use Bias and Gain
1: AI1 Custom V/Hz
2: AI2 Custom V/Hz
3: AI1 & AI2 Custom V/Hz
4: AI3 Custom V/Hz
5: AI1 & AI3 Custom V/Hz
6: AI2 & AI3 Custom V/Hz
7: All Custom V/Hz
0
This parameter selects the type of V/Hz calculation to be used by each Analog Input.
Detailed Descriptions of P4.24 AI V/Hz Calculated Selection Settings
Setting: Function Function Description
0: All Inputs Use
Bias and Gain
All analog input signals are calculated by using bias and gain (P4�10~P4�23)�
1: AI1 Custom V/Hz
AI1 is calculated by using frequency and voltage/current in Low/Mid/
High-Point format (P4�25~P4�48)� Other analog input signals are calculated by
using bias and gain�
2: AI2 Custom V/Hz
AI2 is calculated by using frequency and voltage/current in Low/Mid/
High-Point format (P4�31~P4�36)� Other analog input signals are calculated by
using bias and gain�
3: AI1 & AI2
Custom V/Hz
AI1 & AI2 are calculated by using frequency and voltage/current in Low/Mid/
High-Point format (P4�25~P4�36)� Other analog input signals are calculated by
using bias and gain�
4: AI3 Custom V/Hz
AI3 is calculated by using frequency and voltage in Low/Mid/High-Point
format (P4�37~P4�48)� Other analog input signals are calculated by using bias
and gain�
5: AI1 & AI3
Custom V/Hz
AI1 & AI3 are calculated by using frequency and voltage/current in Low/Mid/
High-Point format (P4�25~P4�30, P4�37~P4�48)� Other analog input signals are
calculated by using bias and gain�
6: AI2 & AI3
Custom V/Hz
AI2 & AI3 are calculated by using frequency and voltage/current in Low/Mid/
High-Point format (P4�31~P4�48)� Other analog input signals are calculated by
using bias and gain�
7: All Custom V/Hz
All analog input signals are calculated by using frequency and voltage/current
in Low/Mid/High-Point format (P4�25~P4�48)�
NOTE: Refer to the detailed Analog Input Example #9 (page 4–121) at the end of these “Group P4.xx Details
Analog Parameters” listings for more information.