Page 4–102
DURApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
Chapter 4: AC Drive Parameters
Type Hex Addr Dec Addr
P4.25 AI1 Low V/A
R/W 0419 41050
Range/Units (Format: 16-bit unsigned) Default
P4�05=0: 0�00~10�00V
P4�05=1: 4�00~20�00mA
P4�05=2: 0�00~20�00mA
P4 �05=0: 0�00V
P4 �05=1: 4�00mA
P4 �05=2: 0�00mA
Type Hex Addr Dec Addr
P4.26 AI1 Low Hz Percent
R/W 041A 41051
Range/Units (Format: 16-bit unsigned) Default
0�00~100�00%
0
Type Hex Addr Dec Addr
P4.27 AI1 Mid V/A
R/W 041B 41052
Range/Units (Format: 16-bit unsigned) Default
P4�05=0: 0�00~10�00V
P4�05=1: 4�00~20�00mA
P4�05=2: 0�00~20�00mA
P4 �05=0: 5�00V
P4 �05=1: 12�00mA
P4 �05=2: 10�00mA
Type Hex Addr Dec Addr
P4.28 AI1 Mid Hz Percent
R/W 041C 41053
Range/Units (Format: 16-bit unsigned) Default
0�00~100�00%
50�00
Type Hex Addr Dec Addr
P4.29 AI1 High V/A
R/W 041D 41054
Range/Units (Format: 16-bit unsigned) Default
P4�05=0: 0�00~10�00V
P4�05=1: 4�00~20�00mA
P4�05=2: 0�00~20�00mA
P4 �05=0: 10�00V
P4 �05=1: 20�00mA
P4 �05=2: 20�00mA
Type Hex Addr Dec Addr
P4.30 AI1 High Hz Percent
R/W 041E 41055
Range/Units (Format: 16-bit unsigned) Default
0�00~100�00%
100�00
Parameters P4.25 to P4.30 are used to configure custom V/Hz settings when the source of the
Frequency Command is a current or voltage analog signal at AI1.