Chapter 4: AC Drive Parameters
Page 4–103
DURApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
Type Hex Addr Dec Addr
P4.31 AI2 Low V/A
R/W 041F 41056
Range/Units (Format: 16-bit unsigned) Default
P4�06=0: 0�00~10�00V
P4�06=1: 4�00~20�00mA
P4�06=2: 0�00~20�00mA
P4 �06=0: 0�00V
P4 �06=1: 4�00mA
P4 �06=2: 0�00mA
Type Hex Addr Dec Addr
P4.32 AI2 Low Hz Percent
R/W 0420 41057
Range/Units (Format: 16-bit unsigned) Default
0�00~100�00%
0
Type Hex Addr Dec Addr
P4.33 AI2 Mid V/A
R/W 0421 41058
Range/Units (Format: 16-bit unsigned) Default
P4�06=0: 0�00~10�00V
P4�06=1: 4�00~20�00mA
P4�06=2: 0�00~20�00mA
P4 �06=0: 5�00V
P4 �06=1: 12�00mA
P4 �06=2: 10�00mA
Type Hex Addr Dec Addr
P4.34 AI2 Mid Hz Percent
R/W 0422 41059
Range/Units (Format: 16-bit unsigned) Default
0�00~100�00%
50�00
Type Hex Addr Dec Addr
P4.35 AI2 High V/A
R/W 0423 41060
Range/Units (Format: 16-bit unsigned) Default
P4�06=0: 0�00~10�00V
P4�06=1: 4�00~20�00mA
P4�06=2: 0�00~20�00mA
P4 �06=0: 10�00V
P4 �06=1: 20�00mA
P4 �06=2: 20�00mA
Type Hex Addr Dec Addr
P4.36 AI2 High Hz Percent
R/W 0424 41061
Range/Units (Format: 16-bit unsigned) Default
0�00~100�00%
100�00
Parameters P4.31 to P4.36 are used to configure custom V/Hz settings when the source of the
Frequency Command is a current or voltage analog signal at AI2.