Page 4–104
DURApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
Chapter 4: AC Drive Parameters
Type Hex Addr Dec Addr
P4.37 AI3 Low Voltage Unipolar
R/W 0425 41062
Range/Units (Format: 16-bit unsigned) Default
0�00~10�00V
0
Type Hex Addr Dec Addr
P4.38 AI3 Low Hz Percent Unipolar
R/W 0426 41063
Range/Units (Format: 16-bit unsigned) Default
0�00~100�00%
0
Type Hex Addr Dec Addr
P4.39 AI3 Mid Voltage Unipolar
R/W 0427 41064
Range/Units (Format: 16-bit unsigned) Default
0�00~10�00V
5�00
Type Hex Addr Dec Addr
P4.40 AI3 Mid Hz Percent Unipolar
R/W 0428 41065
Range/Units (Format: 16-bit unsigned) Default
0�00~100�00%
50�00
Type Hex Addr Dec Addr
P4.41 AI3 High Voltage Unipolar
R/W 0429 41066
Range/Units (Format: 16-bit unsigned) Default
0�00~10�00V
10�00
Type Hex Addr Dec Addr
P4.42 AI3 High Hz Percent Unipolar
R/W 042A 41067
Range/Units (Format: 16-bit unsigned) Default
0�00~100�00%
100�00
Parameters P4.37 to P4.42 are used to configure custom V/Hz settings when the source of the
Frequency Command is a unipolar voltage analog signal at AI3.
Type Hex Addr Dec Addr
P4.43 -AI3 High Voltage Bipolar
R/W 042B 41068
Range/Units (Format: 16-bit signed) Default
–10�00V to 0�00V
0�00
Type Hex Addr Dec Addr
P4.44 -AI3 High Hz Percent Bipolar
R/W 042C 41069
Range/Units (Format: 16-bit signed) Default
–100�00% to +100�00%
0�00
Type Hex Addr Dec Addr
P4.45 -AI3 Mid Voltage Bipolar
R/W 042D 41070
Range/Units (Format: 16-bit signed) Default
–10�00V to 0�00V
–5�00
Type Hex Addr Dec Addr
P4.46 -AI3 Mid Hz Percent Bipolar
R/W 042E 41071
Range/Units (Format: 16-bit signed) Default
–100�00% to +100�00%
–50�00
Type Hex Addr Dec Addr
P4.47 -AI3 Low Voltage Bipolar
R/W 042F 41072
Range/Units (Format: 16-bit signed) Default
–10�00V to 0�00V
–10�00
Type Hex Addr Dec Addr
P4.48 -AI3 Low Hz Percent Bipolar
R/W 0430 41073
Range/Units (Format: 16-bit signed) Default
–100�00% to +100�00%
–100�00
Parameters P4.43 to P4.48 are used to configure custom V/Hz settings when the source of the
Frequency Command is a bipolar voltage analog signal at AI3.