Chapter 5: Serial Communications
Page 5–19
DuRApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
gs4 baCneT objeCT and properTy
In GS4, BACnet supports three object types: Device, AnalogValue (AV), and BinaryValue (BV), as
shown in the following list.
GS4 Supported BACnet Objects and Properties List
Property ID
Object Type
Device
Analog
Value
Binary
Value
#4
ACTIVE TEXT
V
#11
APDU_TIMEOUT
V
#12
APPLICATION_SOFTWARE_VERSION
V
#28
DESCRIPTION
V V V
#30
DEVICE ADDRESS BINDING
V V
#36
EVENT STATE
V V
#44
FIRMWARE_REVISION
V
#46
INACTIVE TEXT
V
#62
MAX_APDU_LENGTH_ACCEPTED
V
#63
MAX_INFO_FRAMES
V
#64
MAX_MASTER
V
#70
MODEL_NAME
V
#73
NUMBER_OF_APDU_RETRIES
V
#75
OBJECT_IDENTIFIER
V* V V
#76
OBJECT_LIST
V
#77
OBJECT_NAME
V* V V
#79
OBJECT_TYPE
V V V
#81
OUT OF SERVICE
V V
#85
PRESENT VALUE
V** V**
#87
PRIORITY ARRAY
V*** V***
#96
PROTOCOL_OBJECT_TYPES_SUPPORTED
V
#97
PROTOCOL_SERVICES_SUPPORTED
V
#98
PROTOCOL_VERSION
V
#104
RELINQUISH DEFAULT
V*** V***
#107
SEGMENTATION_SUPPORTED
V
#111
STATUS FLAGS
V V
#112
SYSTEM_STATUS
V
#117
UNITS
V
#120
VENDOR_IDENTIFIER
V
#121
VENDOR_NAME
V
#139
PROTOCOL_REVISION
V
#155
DATABASE_REVISION
V
* The Object_ID and Object_Name Properties of Device are writeable.
** The Present_Value Property of some AV and BV objects is writeable.
*** Only Writeable objects support Priority_Array and Relinquish_Default.