Page 6–22
DuRApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
Chapter 6: Maintenance and Troubleshooting
Fault Name
Fault Code
in Status
Monitor 1
Fault
Descriptions
Corrective Actions
Can be
Bypassed
in Fire
Mode
(Yes / no)
LOCAL
Fault
CE1
PC Cmd Error
54
Illegal function
code
Check if the function code is correct (function
code must be 03, 06, 10, 63)�
no
LOCAL
Fault
CE2
PC Address Error
55
Illegal data address
(00H to 254H)
Check if the communication address is correct� no
LOCAL
Fault
CE3
PC Data Error
56
Illegal data value Check if the data value exceeds max/min value� no
LOCAL
Fault
CE4
PC Slave Fault
57
Data is written to
read-only address
Check to see if the correct communication
address is being utilized�
no
LOCAL
Fault
CE10
PC TimeOut
58
Modbus
transmission time-
out
For a CE10 Fault to be displayed, the User must
first have enabled the communication time out
detection (P9�03 is not 3 and P9�05 is not 0)�
Should the drive not receive a message from the
host computer (such as PC, HMI, PLC…) for the
time set in P9�05 the drive will trigger the CE10
fault�
Corrective action is to restore the
communication between the host computer and
the drive with messaging set lower/faster than
the time set in P9�05�
no
LOCAL
Fault
CP10
Keypad Timeout
59
Keypad
transmission time-
out
For a CP10 Fault to be displayed the User
must first enable the communication time out
detection (P8�13 is not 3 and P8�14 is not 0)�
Should the drive not receive a message from
Keypad for the time set in P8�14, the Drive will
trigger the CP10 fault�
Corrective action is to restore the
communication between Keypad and the drive�
Typical use for this parameter is for Remote
Keypad use and monitoring of healthy Keypad
to Drive communication�
no
LOCAL
Fault
bF
Braking Fault
60
Brake resistor fault
If the fault code is still displayed on the keypad
after pressing “RESET” key, please return to the
factory
no
(continued next page)