Page 2–18
DuRApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
Chapter 2: Installation and Wiring
14)
Do not monitor the signals on the circuit board while the GS4 AC drive is in operation�
15)
GS4 series AC drives cannot be used with single-phase motors
16)
Route the power and control wires separately, or at 90 degree angle to each other
17)
Ground both ends of the shield wire or conduit for the power wiring�
a) If using a “VFD cable,” follow the manufacturers recommendation for grounding the cable
shield�
b) If using conduit, bond and ground conduit according to applicable electrical codes�
18)
If a filter is required for reducing EMI (Electro Magnetic Interference), install it as close as
possible to the GS4 AC drive� EMI can also be reduced by lowering the Carrier Frequency
Please refer to the “Applied EMI/RFI Techniques” white paper at support�automationdirect�com
19)
If the GS4 AC drive is installed in a place where a load reactor is needed, install the reactor
close to the T1, T2, and T3 side of GS4 AC drive� Do not use a Capacitor, L-C Filter (Inductance-
Capacitance), or R-C Filter (Resistance-Capacitance)�
20)
When using a GFCI (Ground Fault Circuit Interrupt), select current sensor with sensitivity of
200mA or higher, and not less than 0�1-second operation time to avoid nuisance tripping�
main poWer Terminals
Do not supply GS4 460VAC models with single-phase power� R/L1, S/L2, and T/L3 have no
phase-sequence requirement; they can be wired in any order
Do NOT start/stop the GS4 AC drive by turning input power ON/OFF� Start/stop the GS4 AC drive
using RUN/STOP commands via control terminals or the keypad� If you must start/stop the GS4
AC drive by turning power ON/OFF, it is recommended to do so only ONCE per hour
ouTpuT Terminals for main CirCuiT
Do not connect phase-compensation, L-C (Inductance-Capacitance) , or R-C (Resistance
Capacitance) capacitors to the output terminals U/T1, V/T2, W/T3 of the GS4 AC drive�
DO NOT connect phase-compensation capacitors or surge absorbers to the output terminals of
the GS4 AC drive�
Use a well-insulated motor suitable for inverter operation�

Table of Contents

Other manuals for Automation Direct DURApulse GS4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automation Direct DURApulse GS4 and is the answer not in the manual?

Automation Direct DURApulse GS4 Specifications

General IconGeneral
BrandAutomation Direct
ModelDURApulse GS4
CategoryController
LanguageEnglish

Related product manuals