Chapter 2: Installation and Wiring
Page 2–23
DuRApulse GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
Main Circuit Wiring Specifications (continued)
AC
Drive
Frame
Size
AC Drive
Model
Wire Range
(AWG [mm
2
])
Terminal
Tightening
Torque
(kg·cm [lb·in])
Max Min
F
GS4-4175
300 MCM x2 [152 x2]
4/0 x2 [107 x2]*
4/0 x2 [107 x2]
3/0 x2 [85 x2]*
200 [173]
GS4-4200
4/0 x2 [107 x2]
G
Terminals R/L11,12; S/L21,22; T/L31,32
GS4-4250
300 MCM x4 [152 x4]
2/0 x4 [67�4 x4]
1/0 x4 [53�5 x4]*
200 [173]
GS4-4300
3/0 x4 [85 x4]
2/0 x4 [67�4 x4]*
Terminals U/T1, V/T2, W/T3, +1/DC+, -/DC-
GS4-4250
500 MCM x2 [253 x2]
400 MCM x2 [203 x2]
300 MCM x2 [152 x2]*
400 [354]
GS4-4300
500 MCM x2 [253 x2]
400 MCM x2 [203 x2]*
* Wiring specifications for drives with optional conduit box
UL installations must use 600V, 75°C or 90°C wires. Use copper wire only.