4
Technical Specifications
30/130 ekr CON 100 – Installation and Operating Manual
4.2 Power Pack
Only the following power packs may be used for the power supply
of the controller including the BST components connected:
Power pack from Puls GmbH
Type ML100.100
BST order number 1ELNT103837
or
Power pack from Mean Well
Type CLG-100-24
BST order number 1ELNT137535
or
Power packs with the following specifications
Output voltage 24V ± max. 10%
(including ripple)
Output power Min. 100 W
Special properties No hiccup
The power packs must fulfil the requirements of the IEC 61010-1
for energy limited current circuits. When being used in countries
that have defined deviations to IEC 61010-1, these must also be
observed.
The 0 V connection of the power pack has to be connected to the
protective conductor system (see the requirements of the IEC
60204-1).
The power pack is not included in the web guiding controller
scope of delivery.