8
Commissioning
72/130 ekr CON 100 – Installation and Operating Manual
8.7 Performing the Material Setup
In order to achieve optimal guiding results, you have to carry out a
material setup during the initial commissioning of the web guiding
system (see Performing the Material Setup, page 85).
During the material setup the controller is automatically adjusted
to the properties of the material to be scanned.
8.8 Adjusting the Controller Gain
During commissioning, you have to set the controller gain.
You have to set the gain for each guiding mode separately.
Fig.30: Display of the controller gain
Adjusting the controller gain
WARNING
Danger of death from actuator movements!
During function tests, parts of your body may be crushed, cut or hit.
►
Make sure that no persons remain in the vicinity of the pivot /
traversing area of machine components that are positioned by
the actuator.
›› The material web is pulled in.
›› The guiding device is not in an end position.
1. Select the desired guiding mode (see Selecting the Guiding
Mode, page 96).
2. Press the Automatic key.
The LED of the key will illuminate.
The controller switches to automatic mode.
3. Press the SETUP key.
The set gain is displayed at the bottom edge of the display
using a bar indicator ① and as a numeric value ②.