Falcon Parameters Appendix A
A-8
*Access Levels:
Read Only = parameter not configurable
OEM = manufacturer only
Service = password required (default password is 9220)
User = no password required
Lead Lag Configuration Force lead rotation time Service 168h 0m min 734
Lead Lag Configuration Lead lag DHW TOD setpoint User 130 170 oF 735
Lead Lag Configuration Boiler off options Service A:boiler off options disabled 736
Lead Lag Configuration All boilers off threshold Service 210 oF 737
Lead Lag Configuration Lead lag slave enable Service A:Disabled 544
Lead Lag Configuration Slave mode Service B:Equalize runtime 564
Lead Lag Configuration Fan during off cycle rate Service 0% % 567
Lead Lag Configuration Slave sequence order Service 0 1 to 8 568
Lead Lag Configuration Lead lag slave demand to firing
delay
Service 1m 0s 3m 0s mmm ss 570
Lead Lag Configuration LL CH ODR max outdoor
temperature
Service 80 140 oF 517
Lead Lag Configuration LL CH ODR min outdoor
temperature
Service 0 140 oF 518
Lead Lag Configuration LL CH ODR low water temperature Service 80 230 oF 519
Lead Lag Configuration LL CH ODR boost time Service 0m 0s mmm ss 520
Lead Lag Configuration LL CH ODR boost maximum off
point
Service 180 oF 521
Lead Lag Configuration LL CH ODR boost step Service 0 oF 524
Lead Lag Configuration LL CH ODR minimum water
temperature
Service 80 230 oF 527
Lead Lag Configuration Lead lag CH outdoor reset enable Service Disabled 548
Table A-1 CFLC Falcon Parameters (Continued)
Parameter Group Parameter Name Access* Min
range
Default Setting Max.
Range
Parameter
Units
Modbus
Register (dec)