Falcon Alert, Hold, Lockout Codes Appendix D
D-16
296 Abnormal Recycle: Interrupted air flow switch was off during Drive to Purge Rate
297 Abnormal Recycle: Interrupted air flow switch was off during Measured Purge Time
298 Abnormal Recycle: Interrupted air flow switch was off during Drive to Lightoff Rate
299 Abnormal Recycle: Interrupted air flow switch was off during Pre-Ignition test
300 Abnormal Recycle: Interrupted air flow switch was off during Pre-Ignition time
301 Abnormal Recycle: Interrupted air flow switch was off during Main Flame Establishing Period
302 Abnormal Recycle: Ignition failed due to interrupted air flow switch was off
303 Abnormal Recycle: ILK off during Drive to Purge Rate
304 Abnormal Recycle: ILK off during Measured Purge Time
305 Abnormal Recycle: ILK off during Drive to Lightoff Rate
306 Abnormal Recycle: ILK off during Pre-Ignition test
307 Abnormal Recycle: ILK off during Pre-Ignition time
308 Abnormal Recycle: ILK off during Main Flame Establishing Period
309 Abnormal Recycle: ILK off during Ignition period
310 Run was terminated due to ILK was off
311 Run was terminated due to interrupted air flow switch was off
312 Stuck reset switch
313 Run was terminated due to fan failure
314 Abnormal Recycle: Fan failed during Drive to Purge Rate
315 Abnormal Recycle: Fan failed during Measured Purge Time
316 Abnormal Recycle: Fan failed during Drive to Lightoff Rate
317 Abnormal Recycle: Fan failed during Pre-Ignition test
318 Abnormal Recycle: Fan failed during Pre-Ignition time
319 Abnormal Recycle: Fan failed during Ignition period
320 Abnormal Recycle: Fan failed during Main Flame Establishing Period
321 Abnormal Recycle: Main Valve off after 10 seconds of RUN
322 Abnormal Recycle: Pilot Valve off after 10 seconds of RUN
323 Abnormal Recycle: Safety Relay off after 10 seconds of RUN
324 Abnormal Recycle: Hardware flame bias
325 Abnormal Recycle: Hardware static flame
326 Abnormal Recycle: Hardware flame current invalid
327 Abnormal Recycle: Hardware flame rod short
328 Abnormal Recycle: Hardware invalid power
329 Abnormal Recycle: Hardware invalid AC line
330 Abnormal Recycle: Hardware SLO flame ripple
331 Abnormal Recycle: Hardware SLO flame sample
332 Abnormal Recycle: Hardware SLO flame bias range
333 Abnormal Recycle: Hardware SLO flame bias heat
334 Abnormal Recycle: Hardware SLO spark stuck
335 Abnormal Recycle: Hardware SLO spark changed
336 Abnormal Recycle: Hardware SLO static flame
337 Abnormal Recycle: Hardware SLO rod shorted
Table D-2 Falcon Alerts (Continued)