EasyManua.ls Logo

Cleaver-Brooks ClearFire CFLC-5000 - LEAD LAG OPERATION; MODBUS FOR EMS COMMUNICATION

Cleaver-Brooks ClearFire CFLC-5000
290 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix E Falcon Lead Lag
E-5
When combining controllers with different software versions in a Falcon lead/lag net-
work, choose one with the most recent software revision as the Master Host (see Sec-
tion 4).
Modbus network connecting all Falcon boiler controllers in the system.
System header pressure sensor (required for lead lag operation).
833-05105 or 833-03577 display for each boiler.**
A Falcon lead lag kit (880-3755 for 15# steam or 880-3756 for 150# steam) is available from
Cleaver-Brooks and includes a system header pressure transmitter and Falcon Program Module for
copying parameter settings from one Falcon to another.
* Software version 3468.2550 or later required.
** If 833-03577, software version 1.4.2 or later required.
3- SPECIFICATIONS
Maximum length of Modbus network (18 AWG 2-conductor shielded or twisted pair
cable): approx. 600 ft (200 m). NOTE - terminating resistors may be necessary for long
cable runs.
Lead lag Modbus baud rate: 38400
EMS Modbus baud rate: user selectable (9600, 19200, 38400)
Refer to appropriate manual for control component environmental specifications.
For more on the Modbus protocol, visit www.modbus-ida.org.
4- FEATURES
Falcon controllers connected in a lead lag network use the Modbus communication bus to
communicate in a ‘Master-Slave’ configuration. The ‘Master’ is a software management service and
is ‘hosted’ by one of the Falcon units in the network. The lead lag Master is not a separate controller
and no additional control panels or devices are required to configure and operate a Falcon lead lag
network. The Master is responsible for all high-level system functions including boiler sequencing
and staging, pump/valve control, and system PID setpoint control.
PID setpoint control - The lead lag Master uses a proportional-integral-derivative algorithm to
maintain system header temperature at a setpoint. Individual boilers are turned on and off as
necessary according to the configured sequence and add/drop-stage methods. PID gain settings
are user-configurable.
Outdoor reset (hot water systems) - Adjusts the setpoint according to outdoor temperature. Uses
an outdoor temperature sensor wired to one of the lead lag slaves’ sensor inputs.
Time of day setpoint (night setback).
Remote enable - system can be enabled from a separate boiler room controller or building energy
management system (EMS).
Remote setpoint (hot water)
Warm weather shutdown (hot water) - uses the outdoor temperature and shuts down the lead lag
system at a setpoint (plus a 4 deg F hysteresis). Can be programmed to shut down immediately
or when current demand for central heat ends.
Frost Protection (hot water) - when an individual slave requires frost protection it notifies the lead
lag Master, which will then activate a pump or if necessary fire a burner.
Pump control (hot water) - 3 configurable relays on each Falcon controller can be controlled in
conjunction with the lead lag Master.

Table of Contents

Related product manuals