ID-DCU-MARINE-2.2.2, ©ComAp – June 2015 - 167 -
ID-DCU-MARINE-2.2.2.pdf
I-AOUT8
Nominal power supply 24 VDC
Power supply range 8 – 36 VDC
Consumption 0,1A – 0,5A depends on supply voltage and load
Mechanical dimensions: 40 x 95 x 45 mm, 35 mm DIN rail mounted
Interface to controller CAN
Operating temperature -30..+70
o
C
Number of analog outputs 8 (not electrically separated)
Output range 0 to 10 VDC
0 to 20 mA (max 500 )
I-RBxx
Number relays: 16 or 8 in sockets
Nominal voltage: 24 VDC
Voltage range: 16,8 – 36 VDC
Relay opens at: 10% of nominal voltage
Electric / mechanic cycles: 100 000 / 10 000 000
Operating temperature range: - 40°C to 70°C
Maximal load: 6 A resistive load at 24VDC
4 A inductive load at 24 VDC
Contacts protection: varistor 14DK390
I-LB+
Power supply range 8 – 36 VDC
Consumption 100mA at 24 V
Mechanical dimensions: 95 x 96 x 43 mm (3.7’x3.8’x1.7’)
35 mm DIN rail mounted
Interface to controller CAN
Interface to modem or PC RS232, RS422, RS485, USB
Operating temperature -30..+70
o
C
Storage temperature -40..+80
o
C
Front panel protection IP 20
IG-IB
Nominal power supply 24 VDC
Power supply range 8 – 36 VDC
Consumption 100 – 300mA
Mechanical dimensions 150 x 160 x 50 mm
35 mm DIN rail mounted
Interface RS232 to controller
RS232 to Modem
CAN bus
Ethernet
Operating temperature -30..+70
o
C
Storage temperature -30..+70
o
C
Front panel protection IP 20