ID-DCU-MARINE-2.2.2, ©ComAp June 2015 - 109 -
ID-DCU-MARINE-2.2.2.pdf
FireAlarmSpeed [ % ] (PRP only)
When Binary input Fire Speed is closed the binary output Clutch Connect opens (this action deactivates
loadsharing mode if it was activated before) and Loadsharing: ThrottlePos is set to Engine params:
FireAlarmSpeed value.
Step: 0,1 % of Requested RPM range.
Range: 0,0 100,0 %
EnLocalSpeed [ ENABLED, DISABLED ]
ENABLED: Engine Values: Speed Request is defined by Engine params: Local speed setpoint that can
be modified by Fast edit function from front panel (4 sec Enter, / , Enter).
DISABLED: Engine Values: Speed Request is changed via Binary inputs Speed Up, Speed Down or via
Logical Analog input Requested RPM.
See Engine Values: Speed Request charts for PRP and AUX / EME / HRB modes.
Local Speed [ % ]
Setpoint specifies Engine Values: Speed Request when Engine params: EnLocalSpeed = ENABLED.
Setpoint can be changed as standard setpoint or by Fast edit function: press Enter for 4 sec, / set value,
press Enter to confirm.
Step: 1 %
Range: 0 100 %
See Engine Values: Speed Request charts for PRP and AUX / EME / HRB modes.
Engine protect
Horn Timeout [ s ]
The maximum amount of time the Binary output Horn is closed (horn, buzzer will sound). If it desired to have
the horn sound until the alarm is cleared then set to zero.
Step: 1s
Range: 0 600 s
RunOnlyBlkDel1 [ s ]
Delay for Engine running Alarms activation group 1 see drawing below.
Step: 1s
Range: 0 60 s
RunOnlyBlkDel2 [ s ]
Delay for Engine running Alarms activation group 2.
Step: 1s
Range: 0 60 s