ID-DCU MARINE functions
Default archives
The ID-DCU MARINE controller can be configured for auxiliary, emergency, combined (constant speed
engines) or propulsion mode engines. The configuration can be changed in the DriveConfig software by
selecting appropriate archive file.
Operational modes
LOC (Local) mode
LOC (Local) mode can be set in any mode mentioned above – AUX, EME, HRB, PRP. ID-DCU MARINE
receives only commands entered from the ID-DCU MARINE front panel in LOC (Local) mode. All external
interfaces – binary inputs Remote Start, Blackout Start, RemRepStart, Remote Stop, Rem Start/Stop
and serial line commands include I-RD-CAN-ID-DCU-MARINE are disabled.
LOC (Local) mode is activated and deactivated using ID-DCU MARINE front panel buttons: Enter + Mode->
to activate, Enter + <-Mode to deactivate. Active LOC (Local) mode is indicated in the upper right corner of
the ID-DCU MARINE display.
OFF mode
All ID-DCU MARINE controller and ID-RPU binary outputs are switched off. Engine can’t be started or
running engine is stopped, prelubrication function is not active. Firmware and controller configuration can be
changed in OFF mode only. OFF mode is available in all applications – AUX, EME, CMB and PRP.