Analog Sensor availability
Table of supported sensors on various modules. Do not configure sensors that are not supported on the
input.
ID AI1-4
ID AI5-8
IGS-PTM
IS-AIN8
IS-AIN8TC
Inteli AIN8
Inteli AIN8TC
PT100/°C
Y
Y
Y
Y
PT1000/°C
Y
Y
Y
Y
NI100/°C
Y
Y
Y
Y
NI1000/°C
Y
Y
Y
Y
PT100/°F
Y
Y
Y
Y
PT1000/°F
Y
Y
Y
Y
NI100/°F
Y
Y
Y
Y
NI1000/°F
Y
Y
Y
Y
Thermo J/°C
Y
Y
Y
Y
Thermo K/°C
Y
Y
Y
Y
Thermo L/°C
Y
Y
Y
Y
Thermo J/°F
Y
Y
Y
Y
Thermo K/°F
Y
Y
Y
Y
Thermo L/°F
Y
Y
Y
Y
4-20mA passive
Y
Y
4-20mA active
Y
Y
Y
Y
Y
0-20mA passive
Y
Y
+-20mA active
Y
Y
Y
Y
Y
0-250
Y
Y
Y
Y
Y
0-2400
Y
Y
Y
Y
0-2.4V
Y
Y
0 4V
Y
0 5V
Y
Y
Tristate
Y
Y
+-1V
Y
Y
Y
0-10V
Y
Y
0-100mV
Y
Y
Y
Hint:
Fahrenheit sensors are supported from IS-AIN8 of sw version 2.2 only.
Analog as Binary input
To use Analog input as binary configure following characteristics:
Primary
Converted
0
0
1000
1
Analog as three state (tristate) binary input
Open, close and failure (broken wire, short wire) states are detected. Threshold level is 750 , failure is
detected when circuit resistance is <10 or > 2400 .

Table of Contents

Other manuals for ComAp InteliDrive DCU Marine

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliDrive DCU Marine and is the answer not in the manual?

ComAp InteliDrive DCU Marine Specifications

General IconGeneral
BrandComAp
ModelInteliDrive DCU Marine
CategoryController
LanguageEnglish

Related product manuals