ID-DCU-MARINE-2.2.2, ©ComAp – June 2015 - 60 -
ID-DCU-MARINE-2.2.2.pdf
InteliDrive local / remote commands blocking overview Y = available; N = blocked
Low Brightness
Active Binary input switches ID-DCU MARINE display backlight between two adjustable intensity levels.
Alternative intensity of the backlight can be set independently by ID-DCU MARINE panel buttons:
1. Hold Enter and press Page to switch to ID Info screen (from any measure screen)
2. Hold Enter and pres / arrow key to increase/decrease display brightness
The adjusted intensity is stored in non-volatile memory.
Hint:
Both backlight levels are default (from production) set to maximum.
Force Block
Active input blocks protections that are configured as “Force Block” Prot. block type. Corresponding setpoint
is ForceBlock del.
Fault Reset
Binary input for Alarm acknowledge (level sensitive) has the same function as controller front panel button
Fault reset (i.e. the acknowledge function is screen sensitive).
Hint:
There is separated acknowledge for ECU Alarms – see Binary input ECU FltReset.
Horn Reset
Binary input Horn Reset is level sensitive.