ID-DCU-MARINE-2.2.2, ©ComAp June 2015 - 62 -
ID-DCU-MARINE-2.2.2.pdf
Blackout Start (AUX, EME, CMB-EME, CMB-HRB)
External “edge sensitive” request for engine start. Input is inactive in LOC (Local) mode. Adjustable number
of attempts (see setpoints Engine params: Crank Attempts, MaxCrank Time and Cranking Pause).
Engine starting signals
Remote Start
Blackout Start
RemRepStart
Panel START button
Input
sensitive
Edge sensitive;
2-nd edge skips Idle
Edge sensitive;
Edge sensitive;
Edge sensitive;
2-nd edge skips Idle
Active in
MODE
AUX; EME; PRP
CMB:EME;
CMB:HRB
AUX; EME
CMB:EME;
CMB:HRB
(PRP not available)
PRP
(other modes
not available)
AUX; EME; PRP
CMB:EME; CMB:HRB
LOC
Inactive in
MODE
LOC
LOC
LOC
- all time active
Number of
starting
attempts
1 x
Engine params:
Crank Attempts
Engine params:
Crank Attempts
1 x
Engine stopping signals
Remote Stop
Panel STOP button
(1 sec holding time for
Stop button activation!)
Input sensitive
Edge sensitive;
2-nd edge skips Cooling
Edge sensitive;
2-nd edge skips Cooling
Active in MODE
AUX; EME; PRP
CMB:EME; CMB:HRB
AUX; EME; PRP
CMB:EME; CMB:HRB
Inactive in
MODE
LOC
-
Hint:
The setpoint Crank Attempts is not followed if Sd Override is active, crank attempts number is then
unlimited in case of Blackout Start.
Back Up Speed (PRP only)
If input is active and Logical Analog input Requested RPM is not valid (out of range, sensor fail),
Loadsharing: ThrottlePos is set to Load sharing: Back Up Speed value. Loadsharing: ThrottlePos = 0,0%
when analog request is out of range and Binary input Back Up Speed is not active.
Fire Speed (PRP only)
If active, clutch is disconnected and Loadsharing: ThrottlePos is set to Engine params: FireAlarmSpeed,
the ThrottlePos value change is influenced by ramp specified by Loadsharing: RQSP Ramp.
Rem Clutch (PRP only)
If active closes binary output Clutch Connect see Clutch Connect (PRP only).
StartBlocking1 .. StartBlocking5
OR logical function of all StartBlocking Logical Binary inputs forces controller NotReady state ( i.e. disables
engine start). It is active in LOC (Local) mode as well.