Second RPM Sw (AUX, EME, CMB only)
The output is closed when setpoint Basic setting: Speed Select = Secondary or Speed Select = BIN.INPUT
and corresponding Binary input BI Secondr RPM is closed. This logical output (Source) can be configured to
corresponding J1939 output (e.g. Frequency Select in Volvo-IndustrialD12 Aux) see an example below.
Stop Pulse
1 sec pulse is generated in the beginning of Stop procedure.
Comm AIN Fail
Communication warning fail when any Analog input module address does not communicate (2s timeout).
Comm BIN Fail
Communication warning fail when any Binary input module address does not communicate (2s timeout).
Comm AOUT Fail
Communication warning fail when any Analog output module address does not communicate (2s timeout).
Comm BOUT Fail
Communication warning fail when any Binary output module address does not communicate (2s timeout).
Nominal/Idle
Inverted function to binary output Idle/Nominal. The output closes during engine start, after Idle Time
setpoint elapses. The output closes again after Cooling Time is finished.
Alarm Blink
Function is based on Binary output Common Alarm - stays closed when any alarm is active (at least one
item in Alarm list) and opens for 2 sec when any new Alarm is activated. The first activation is delayed 2 sec.
No Fault reset influence when at least one alarm is active. Output opens when Alarm list is empty.
Nominal Sw
The output is closed when setpoint Basic setting: Idle/Nominal = NOMINAL or Idle/Nominal = BIN.INPUT
and corresponding Binary input BI Nominal is closed. This logical output (Source) can be configured to
corresponding J1939 output (e.g. Idle Speed Select in Volvo-IndustrialD12 Aux).
Logical 0
Constant value that can be configured to any output (e.g. CurrentGear in Volvo-PRP).
Logical 1
Constant value that can be configured to any output (e.g. CurrentGear in Volvo-PRP).