ID-DCU-MARINE-2.2.2, ©ComAp June 2015 - 88 -
ID-DCU-MARINE-2.2.2.pdf
In example above there is Wrn limit type set to Const = 60.
There is visible setpoint corresponding to Wrn, Over protection. It is possible to change limit name,
value and limits.
Use “+” button to add new limit for the third (Wrn, Under) protection. Name “Limit3” can be changed.
Limit and Delay type must be in this case set to “Setpoint”