ID-DCU-MARINE-2.2.2, ©ComAp June 2015 - 92 -
ID-DCU-MARINE-2.2.2.pdf
2. Reading form J1939
J1939 value
logical function
Please note there can be configured Protection as well.
Protection types
Warning
Indication only (no engine stop)
Shutdown
Fast engine stop
Cooldown
Engine stop with cooling period
Fail sensor
Measured value is out of sensor characteristics.
Warning+BW
Indication + Broken wire detection
Shutdown+BW
Shut down + Broken wire detection
Warning + Fls
Warning is activated in the case of sensor fail as well
Shutdown + Fls
Shut down is activated in the case of sensor fail as well
Sd override
This protection stays active in the case of Sd override is activated.
Alarm only
Only Alarm list indication, disappear without confirmation
HistRecOnly
History record only