IOLINK Block
Statistics tab
R301.1 Experion C300 Controller User's Guide 131
11/06 Honeywell
Plain Text Parameter Name
User
Configurable
Notes
Token Stall Time
IOSSTALLTIME
No
Defines the period of
time (currently 200us /
10ms worst case) that
is allocated to handle
critical activities other
than I/O link traffic.
Average I/O Link Requests per Second
Cache
CFIFORATEA
No
Shows the average
number of parameters
accessed through
cache FIFO per second.
Process Data
PDFIFORATEA
No
Shows the average
number of parameters
accessed through
process data FIFO per
second.
Write
WRFIFORATEA
No
Shows the average
number of parameters
accessed through Write
FIFO per second.
Supervisor
SUPVFIFORATEA
(Currently not used)
No
Indicates the average
number of parameters
accessed through
Supervisor FIFO per
second.
Local Data Transfer
LCDXFIFORATEA
No
Indicates the average
number of parameters
accessed through Local
Data Transfer FIFO per
second.
Maximum I/O Link Requests Per Second
Cache
CFIFORATEM
No
Shows the maximum
number of parameters
accessed through
cache FIFO per second.