Control Builder block icon descriptions
FTE activity LEDs
170 Experion C300 Controller User's Guide R301.1
Honeywell 11/06
Icon Represents . . .
C300 Controller
(C300STATE)
(yellow)
C300 is non-redundant No Database
(yellow & white)
Primary C300 is synchronized No Database
(yellow & yellow)
Primary C300 is not synchronized and partner
C300 is visible
No Database
(yellow &
shadow)
Primary C300 is not synchronized and partner
C300 is absent or incompatible
No Database
(blue)
C300 is non-redundant. Idle
(blue & white)
Primary C300 is synchronized Idle
(blue & white,
pause)
Primary C300, standby synchronization Idle
(blue & yellow)
Primary C300 is not synchronized and partner
C300 is visible.
Idle
(blue & shadow)
Primary C300 is not synchronized and partner
C300 is absent or incompatible.
Idle
(green)
C300 is non-redundant Run or OK
(green & white)
Primary C300 is synchronized Run or OK
(green & white,
pause)
Primary C300, standby synchronization Run or OK
(green & yellow)
Primary C300 is not synchronized and partner
C300 is visible
Run or OK
(green &
shadow)
Primary C300 is not synchronized and partner
C300 is absent or incompatible
Run or OK
(white & green)
Secondary C300 is synchronized Backup
(white & green,
Secondary C300, standby synchronization Backup