C300 Redundancy-related notifications 
Become Primary command – BECMPRICMD 
202  Experion C300 Controller User's Guide   R301.1 
 Honeywell 11/06 
Notification Description RDNSYNCSTATE 
Note that partner compatibility checks across the 
redundancy private-path are periodically attempted when in 
the NOPARTNER sync state.   
Redun Sync in 
Progress 
Both the primary and secondary controllers generate this 
notification upon commencing initial-sync.   
SYNCINPROG 
Redun Sync 
Maintenance 
Both the primary and secondary controllers generate this 
notification upon successfully completing initial-sync.   
SYNCMAINT 
Redun Standby  Both the primary and secondary controllers generate this 
notification upon entering the Standby sync state either via 
the Enable Standby command or due to On Process 
Migration.   
STANDBY 
Redundancy Link 
Active  
One time information notification sent whenever the 
redundancy link transitions from link inactive to link active.  
For example, this notification will be generated when the 
redundancy link cable is connected.   
 
Redundancy Link 
Inactive 
One time information notification sent whenever the 
redundancy link transitions from link active to link inactive.  
For example, this notification will be generated when the 
redundancy link cable is disconnected.   
 
Switchover  Both the primary and secondary controllers generate this 
notification following controller redundancy switchover.  
Specifically, switchover breaks the previously existing 
notification connection, a new notification connection is 
reformed, event regeneration is commanded, and then the 
controller generates this notification.  This notification is 
generated on subsequent commanded event regenerations 
until initial-sync is attempted.   
 
Sync Checksum 
Fail 
The primary and secondary controllers perform a continuous 
background checksum on redundancy tracked memory to 
explicitly verify that the primary and secondary are in sync.  
Failure of this diagnostic indicates that the secondary has 
encountered a condition whereby its local copy of 
redundancy memory does not match the primary.  This fault 
is inserted either by {1} a software bug on secondary 
controller firmware whereby redundancy tracked memory is 
overwritten by code running on the secondary, or {2} 
marginal hardware.  Given that firmware releases are 
formally tested with redundant controllers prior to 
distribution, marginal hardware is the most likely culprit.  
Moreover, the full redundancy communication path has to be 
considered: 
In C200 controllers: 
Primary CPM Î Primary backplane Î Primary RM Î Fiber