C300 Controller installation
To install a C300 Controller
R301.1 Experion C300 Controller User's Guide 25
11/06 Honeywell
Step Action
4
Connect FTE-A and FTE-B Ethernet link cables to the RJ-45 connectors on
C300 IOTA board.
The Yellow Cat5 cable connects to the FTEA” connector on the IOTA.
The Green Cat5 cable connects to the FTEB” connector on the IOTA.
5
Route the FTE cables to the appropriate Control Firewall module location.
The Yellow FTE cable is routed to the Control Firewall that supports FTE-
A.
The Green FTE cable is routed to the Control Firewall that supports FTE-
B.
6
If using the IOLINK interface in the controller, connect IOLink cable pairs to
IOTA board.
Four connectors on the IOTA provide redundant support for two IOLink
interfaces IOLINK 1 (Gray) and IOLINK 2 (Violet). IOLink cable pairs include
multidrop connectors to connect other I/O components to the IOLink.
Connect IOLINK cable pair to IOL1A and IOL1B for IOLINK 1 interface of
the controller.
Connect a second IOLINK cable pair to IOL2A and IOL2B for IOLINK 2
interface of the controller.