Configure CEEC300 block 
To configure a CEEC300 function block 
44  Experion C300 Controller User's Guide   R301.1 
 Honeywell 11/06 
Step Action  Result 
6 
Accept the default or click 
 down-
arrow button and select desired user. 
Press <Tab>. 
Moves cursor to User Lock for CEE Idle 
field. 
7 
Accept the default or click 
 down-
arrow button and select desired user. 
Press <Tab>. 
Moves cursor to Program Access may 
command CEE from Idle to Run check 
box. 
8 
Add a check to the box if you want to 
enable access.  Press <Tab>. 
Moves cursor to Program Access may 
command CEE from Run to Idle check 
box.  
9 
Add a check to the box if you want to 
enable access.  Press <Tab>. 
Moves cursor to the Alarming Enabled 
check box.   
10 
Accept the default (Alarming Enabled), or 
uncheck the box to disable alarming 
function.   Press <Tab>. 
Moves cursor to the Enable Memory 
Limit Exceeded Alarm check box. 
11 
Accept the default (Memory Limit 
Exceeded Alarm enabled), or uncheck 
the box to disable alarming function.  
Press <Tab>. 
Moves cursor to the Powerup Restart 
Settings for CEE State. 
12 
Accept the default or click 
 down-
arrow button and select desired state.  
Note that if you select LASTTIMEOUT 
state, then the Warm Timeout field is 
active.  
13 
If the Warm Timeout field is active, 
accept the default or key in desired 
timeout value. Press <Tab>. 
Moves cursor to Batch Events Memory 
field. 
 
Accept the default or click 
 down-
arrow button and select desired state.  
Press <Tab>. 
Moves cursor to the Time Zone field. 
15 
Enter the appropriate value for the time 
zone of the controller location. Press 
<Tab>. 
Moves cursor to the Daylight Savings 
Time check box. 
16 
Add a check to the box if Daylight 
Savings Time is in effect for this location.  
Press <Tab>. 
Moves cursor to the Year Format field.