Configure CEEC300 block
To configure a CEEC300 function block
44 Experion C300 Controller User's Guide R301.1
Honeywell 11/06
Step Action Result
6
Accept the default or click
down-
arrow button and select desired user.
Press <Tab>.
Moves cursor to User Lock for CEE Idle
field.
7
Accept the default or click
down-
arrow button and select desired user.
Press <Tab>.
Moves cursor to Program Access may
command CEE from Idle to Run check
box.
8
Add a check to the box if you want to
enable access. Press <Tab>.
Moves cursor to Program Access may
command CEE from Run to Idle check
box.
9
Add a check to the box if you want to
enable access. Press <Tab>.
Moves cursor to the Alarming Enabled
check box.
10
Accept the default (Alarming Enabled), or
uncheck the box to disable alarming
function. Press <Tab>.
Moves cursor to the Enable Memory
Limit Exceeded Alarm check box.
11
Accept the default (Memory Limit
Exceeded Alarm enabled), or uncheck
the box to disable alarming function.
Press <Tab>.
Moves cursor to the Powerup Restart
Settings for CEE State.
12
Accept the default or click
down-
arrow button and select desired state.
Note that if you select LASTTIMEOUT
state, then the Warm Timeout field is
active.
13
If the Warm Timeout field is active,
accept the default or key in desired
timeout value. Press <Tab>.
Moves cursor to Batch Events Memory
field.
Accept the default or click
down-
arrow button and select desired state.
Press <Tab>.
Moves cursor to the Time Zone field.
15
Enter the appropriate value for the time
zone of the controller location. Press
<Tab>.
Moves cursor to the Daylight Savings
Time check box.
16
Add a check to the box if Daylight
Savings Time is in effect for this location.
Press <Tab>.
Moves cursor to the Year Format field.