Reset Device Index and IP address of a controller
To configure IOLINK blocks
56 Experion C300 Controller User's Guide R301.1
Honeywell 11/06
network, or when moving a controller to a different node, another FTE network, another
server domain or another system.
WARNING
Be sure that the controller is in its IDLE or safe state before initiating a
shutdown.
Use this procedure to assign a new Device Index and IP Address to a controller installed
in the system.
Step Action
1
If you are only assigning another Device Index to a controller – Go to Step 5.
If moving the controller to a different location or FTE network – Go to Step 2.
2
Shutdown the controller using Control Builder. See Initiating a Shutdown
.
3
Uninstall the controller module and IOTA.
4
Refer to the procedure C300 Controller installation to install the controller in
its new location.
5
Shutdown the controller using Control Builder. See Initiating a Shutdown
.
6
Set the FTE DEVICE INDEX rotary switches on the controller IOTA to the
new Device Index.
7
Using ESD precautions, short the two RESET pads on the right side of the
IOTA, (labeled RP) to restart the controller.
8
Upon restart, the controller will:
Clear its user memory database and transition to the NODB state.
Clear the old Device Index retained in memory
Assume the new Device Index set in the FTE DEVICE INDEX and request
an IP Address based on this new Device Index.
9
In Control Builder, configure as a new controller. See C300 Controller
Configuration for the procedure.