Assign Control Modules and IOMs to a CEEC300 block
To assign Control Modules and IOMs to a CEE
R301.1 Experion C300 Controller User's Guide 65
11/06 Honeywell
Step Action Result
6
Click listed IOM to be assigned.
Highlights selection and applicable CEEs
appear in Assign To list.
7
Accept default CEE selection or click
desired CEE in list.
Be sure correct CEE is selected in list.
8
Click the
assign button.
Selected IOM is assigned to the selected
CEE and appears in the Assigned
Modules list.
9
Repeat Steps 2 to 4 to assign other
CMs/SCMs. Or, repeat Steps 5 to 8 to
assign other IOMs.
Complete CM, SCM, and IOM
assignments.