C300 Controller Block
Redundancy tab
R301.1 Experion C300 Controller User's Guide 81
11/06 Honeywell
Plain Text Parameter Name
User
Configurable
Notes
Last Synchronization
Time
SYNCTIMEBEG
No
Shows system time when
initial synchronization was
completed.
Last Lost of Sync
Time
SYNCTIMEEND
No
Shows system time when
last synchronization was
lost.
Redundancy
Controllability
RDNCTLABILITY
No
Shows whether the current
controller is Better, Equal,
or Worse to be the primary
controller (as compared to
the partner controller).
Device Index
RDNDEVICEIDX
No
Shows the Device Index of
the redundant secondary
controller.
Redundancy Statistics
Traffic Redundancy
(bytes/sec)
RDNXFERAVG
No
Current amount of
redundancy data traffic
across the redundancy
private path, in bytes per
second.
Max Redundancy
Traffic (bytes/sec)
RDNXFERMAX
No
Maximum amount of
redundancy data traffic
across the redundancy
private path throughput
since power up or last
statistics reset.
Redundancy Delay
(%)
RDNDELAYAVG
No
The average of
redundancy delay CPU in
percent.
Max Redundancy
Delay (%)
RDNDELAYMAX
No
Historical maximum
redundancy delay CPU
value observed since
power up or last statistics
reset.

Table of Contents