Appendix A—Description of parameters
VARIABLE SPEED DRIVE SERIES III LIT-12012999—June 2018 www.johnsoncontrols.com
Code Modbus ID Parameter Application RO/RW
P10.1.22 1710 RTC Clock Fault Bypass Enable 1,2,3 RW
This parameter specifies whether an automatic switch to bypass when an Charge Switch fault occurs.
0 = Disable Auto bypass on Charge Switch fault
1 = Enable Auto bypass on Charge Switch fault
P10.1.23 1711 Ctrl Board OverTemp Fault Bypass Enable 1,2,3 RW
This parameter specifies whether an automatic switch to bypass when an Charge Switch fault occurs.
0 = Disable Auto bypass on Charge Switch fault
1 = Enable Auto bypass on Charge Switch fault
P10.1.24 1712 Speed Search Start Fault Bypass Enable 1,2,3 RW
This parameter specifies whether an automatic switch to bypass when an Speed Search Start
fault occurs.
0 = Disable Auto bypass on Speed Search Start fault
1 = Enable Auto bypass on Speed Search Start fault
P10.1.25 1713 Fieldbus Fault Bypass Enable 1,2,3 RW
This parameter specifies whether an automatic switch to bypass when an Fieldbus fault occurs.
0 = Disable Auto bypass on Fieldbus fault
1 = Enable Auto bypass on Fieldbus fault
P10.2.1 2476 Redundant Drive Enable 2,3 RW
Use this parameter to enable the Redundant drive setup where multiple drives can be connected via
Para communications to start if the main drive fails or runtime settings below expires.
P10.2.2 2278 Drive ID 2,3 RW
Use this parameter to set the drive address when using multi drive redundant mode, based off this id the
drive enables in the desired sequence and can be monitored at this drive ID value in the monitor screen.
P10.2.3 2477 Redundant Run Time Enable 2,3 RW
Use this parameter to enables the Run time limit for the Redundant drive mode so that drives will be
cycled based off the Run time limit value.
P10.2.4 2478 Redundant Run Time Reset 2,3 RW
Use this parameter to manually Reset the Redundant Drive Run timer.
P10.2.5 2479 Redundant RunTime Limit 2,3 RW
Use this paramter to set the time limit for Run time of the drive when enabled for the Redundant
drive scheme.
P11.1.1 2487 Interval 1 Setting 2,3 RW
Use this parameter with the Interval time setting for interval 1 to set the desired time frame for the
selection; to be Weekly or Daily.
0 - Weekly - would setup the timer for the week long. Drive starts on the on day/time and runs to the
stop day and time.
1 - Daily - would setup the timer for the defined day. Drive starts on time and stops on that day off time,
for the listed days in the sequence
P11.1.2 491 Interval 1 On Time 2,3 RW
Use this parameter to set the on time for Interval function. It uses 24-hour format. Use to specify a time
of day for a desired function to be disabled.
P11.1.3 493 Interval 1 Off Time 2,3 RW
Use this parameter to set the off time for Interval function. It uses 24-hour format. Use to specify a time
of day for a desired function to be disabled.
P11.1.4 517 Interval 1 From Day 2,3 RW
Use this parameter to set the day of week for Interval function to start on.
0 = Sunday
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls VS3 Series and is the answer not in the manual?

Johnson Controls VS3 Series Specifications

General IconGeneral
BrandJohnson Controls
ModelVS3 Series
CategoryInverter
LanguageEnglish

Related product manuals