196
Appendix A—Description of parameters
VARIABLE SPEED DRIVE SERIES III LIT-12012999—June 2018 www.johnsoncontrols.com
Code Modbus ID Parameter Application RO/RW
P11.6.5 515 Timer 3 Duration 2,3 RW
Use this parmeter to set the duration of time the timer will run when activated. (Activated by DI)
P11.6.6 534 Timer 3 Channel 2,3 RW
Use this parameter to assign the interval to a select time channel to store the timer channel.
0 = Not used
1 = Time channel 1
2 = Time channel 2
3 = Time channel 3
P12.1.1 2533 FB Process Data Input 1 Sel 1,2,3 RW
Use this parameter to assign the Fieldbus Data Input Selections, parameter/monitor Para ID's can be
assigned to these registers and then written over the desired Fieldbus Network Word for Process Data.
See Communication Manual for more details.
P12.1.2 2534 FB Process Data Input 2 Sel 1,2,3 RW
Use this parameter to assign the Fieldbus Data Input Selections, parameter/monitor Para ID's can be
assigned to these registers and then written over the desired Fieldbus Network Word for Process Data.
See Communication Manual for more details.
P12.1.3 2535 FB Process Data Input 3 Sel 1,2,3 RW
Use this parameter to assign the Fieldbus Data Input Selections, parameter/monitor Para ID's can be
assigned to these registers and then writen over the desired Fieldbus Network Word for Process Data.
See Communication Manual for more details.
P12.1.4 2536 FB Process Data Input 4 Sel 1,2,3 RW
Use this parameter to assign the Fieldbus Data Input Selections, parameter/monitor Para ID's can be
assigned to these registers and then written over the desired Fieldbus Network Word for Process Data.
See Communication Manual for more details.
P12.1.5 2537 FB Process Data Input 5 Sel 1,2,3 RW
Use this parameter to assign the Fieldbus Data Input Selections, parameter/monitor Para ID's can be
assigned to these registers and then written over the desired Fieldbus Network Word for Process Data.
See Communication Manual for more details.
P12.1.6 2538 FB Process Data Input 6 Sel 1,2,3 RW
Use this parameter to assign the Fieldbus Data Input Selections, parameter/monitor Para ID's can be
assigned to these registers and then writen over the desired Fieldbus Network Word for Process Data.
See Communication Manual for more details.
P12.1.7 2539 FB Process Data Input 7 Sel 1,2,3 RW
Use this parameter to assign the Fieldbus Data Input Selections, parameter/monitor Para ID's can be
assigned to these registers and then written over the desired Fieldbus Network Word for Process Data.
See Communication Manual for more details.
P12.1.8 2540 FB Process Data Input 8 Sel 1,2,3 RW
Use this parameter to assign the Fieldbus Data Input Selections, parameter/monitor Para ID's can be
assigned to these registers and then written over the desired Fieldbus Network Word for Process Data.
See Communication Manual for more details.
P12.2.1 1556 FB Process Data Output 1 Sel 1,2,3 RW
Use this parameter to accessing the Fieldbus Data Output Selections, parameter/monitor ID's can be
assigned to these registers and then read over the desired Fieldbus Network Word for Process Data.
Default Values for Process Data Out in Fieldbus(build table for below values)
Process Data Out1 - Output Frequency = ID 1
Process Data Out2 - Motor Speed = ID 2
Process Data Out3 - Motor Current = ID 3
Process Data Out4 - Motor Torque = ID 4
Process Data Out5 - Motor Power = ID 5
Process Data Out6 - Motor Voltage = ID 6
Process Data Out7 - DC Link Voltage = ID 7
Process Data Out8 - Active Fault Code = ID 28
See Communication Manual for more details.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls VS3 Series and is the answer not in the manual?

Johnson Controls VS3 Series Specifications

General IconGeneral
BrandJohnson Controls
ModelVS3 Series
CategoryInverter
LanguageEnglish

Related product manuals