L-Gate User Manual 145 LOYTEC
Version 3.2 LOYTEC electronics GmbH
Property Identifier Property Datatype Conformance Code
Object_Identifier BACnetObjectIdentifier R
Object_Name CharacterString R
Object_Type BACnetObjectType R
System_Status BACnetDeviceStatus R
Vendor_Name CharacterString R
Vendor_Identifier Unsigned16 R
Model_Name CharacterString R
Firmware_Revision CharacterString R
Application_Software_Version CharacterString R
Location CharacterString R
Description CharacterString R
Protocol_Version Unsigned R
Protocol_Revision Unsigned R
Protocol_Services_Supported BACnetServicesSupported R
Protocol_Object_Types_Supported BACnetObjectTypesSupported R
Object_List BACnetARRAY[N]of
BACnetObjectIdentifier
R
Max_APDU_Length_Accepted Unsigned R
Segmentation_Supported BACnetSegmentation R
Max_Segments_Accepted Unsigned R
APDU_Segment_Timeout Unsigned R
APDU_Timeout Unsigned R
Number_Of_APDU_Retries Unsigned R
Max_Master Unsigned(1..127) R
Max_Info_Frames Unsigned R
Device_Address_Binding List of BACnetAddressBinding R
Database_Revision Unsigned R
Active_COV_Subscriptions List of BACnetCOVSubscription R
Profile_Name CharacterString R
Table 10: Properties of the Device Object
7.3.1.1 Object_Identifier (Read-Only)
This property, of type “BACnetObjectIdentifier”, is a numeric code that is used to identify
the object. For the Device object, the object identifier is unique internetwork-wide.
The “Object Type” part of the “Object_Identifier” is 8 (=device). The “Instance” part of
this property is configurable via the configuration UI (see Section 4.2.7). The default value
for the “Instance” part is 17800.
7.3.1.2 Object_Name (Read-Only)
The value of this property is configurable via the configuration UI (see Section 4.2.7).
The default value is “L-Gate”. Note that this name must be unique in the BACnet
internetwork.
7.3.1.3 Object_Type (Read-Only)
The value of this property is DEVICE (8).