L-Gate User Manual 146 LOYTEC
Version 3.2 LOYTEC electronics GmbH
7.3.1.4 System_Status (Read-Only)
The value of this property is always OPERATIONAL.
7.3.1.5 Vendor_Name (Read-Only)
The value of this property is “LOYTEC electronics GmbH”.
7.3.1.6 Vendor_Identifier (Read-Only)
The value of this property is 178.
7.3.1.7 Model_Name (Read-Only)
The value of this property is equal to the product code of the device (“LGATE-900”).
7.3.1.8 Firmware_Revision (Read-Only)
The value of this property gives the current firmware version of the device.
7.3.1.9 Application_Software_Version (Read-Only)
The value of this property gives the build date and the version of the current firmware.
7.3.1.10 Location (Read-Only)
This property is configurable via the configuration UI (see Section 4.2.7). The default
value is “unknown”.
7.3.1.11 Description (Read-Only)
This property is configurable via the configuration UI (see Section 4.2.7). The default
value is “L-Gate”.
7.3.1.12 Protocol_Version (Read-Only)
The value of this property is 1.
7.3.1.13 Protocol_Revision (Read-Only)
The value of this property is 4.
7.3.1.14 Protocol_Services_Supported (Read-Only)
For the services supported please refer to the LGATE-900 PICS document.
7.3.1.15 Protocol_Object_Types_Supported (Read-Only)
For the supported object types please refer to the LGATE-900 PICS document.
7.3.1.16 Object_List (Read-Only)
This read only property is a BACnetARRAY of “Object_Identifiers”, one
“Object_Identifier” for each object within the device that is accessible through BACnet
services (see below).
7.3.1.17 Max_APDU_Length_Accepted (Read-Only)
The value of this property is 487 if BACnet MS/TP is used and 1473 if BACnet/IP is used.
7.3.1.18 Segmentation_Supported (Read-Only)
The value of this property is SEGMENTED_BOTH.