EasyManua.ls Logo

LOYTEC L-Gate - Page 146

Default Icon
161 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
L-Gate User Manual 146 LOYTEC
Version 3.2 LOYTEC electronics GmbH
7.3.1.4 System_Status (Read-Only)
The value of this property is always OPERATIONAL.
7.3.1.5 Vendor_Name (Read-Only)
The value of this property is “LOYTEC electronics GmbH”.
7.3.1.6 Vendor_Identifier (Read-Only)
The value of this property is 178.
7.3.1.7 Model_Name (Read-Only)
The value of this property is equal to the product code of the device (“LGATE-900”).
7.3.1.8 Firmware_Revision (Read-Only)
The value of this property gives the current firmware version of the device.
7.3.1.9 Application_Software_Version (Read-Only)
The value of this property gives the build date and the version of the current firmware.
7.3.1.10 Location (Read-Only)
This property is configurable via the configuration UI (see Section 4.2.7). The default
value is “unknown”.
7.3.1.11 Description (Read-Only)
This property is configurable via the configuration UI (see Section 4.2.7). The default
value is “L-Gate”.
7.3.1.12 Protocol_Version (Read-Only)
The value of this property is 1.
7.3.1.13 Protocol_Revision (Read-Only)
The value of this property is 4.
7.3.1.14 Protocol_Services_Supported (Read-Only)
For the services supported please refer to the LGATE-900 PICS document.
7.3.1.15 Protocol_Object_Types_Supported (Read-Only)
For the supported object types please refer to the LGATE-900 PICS document.
7.3.1.16 Object_List (Read-Only)
This read only property is a BACnetARRAY of “Object_Identifiers”, one
“Object_Identifier” for each object within the device that is accessible through BACnet
services (see below).
7.3.1.17 Max_APDU_Length_Accepted (Read-Only)
The value of this property is 487 if BACnet MS/TP is used and 1473 if BACnet/IP is used.
7.3.1.18 Segmentation_Supported (Read-Only)
The value of this property is SEGMENTED_BOTH.

Table of Contents