Chapter 6 - Parameter Description [FU2]
6-26
[Power ON Start: ā€˜No’]
[Power ON Start: ā€˜Yes’]
Note: In case of using ā€˜Power ON Start’ to ā€˜Yes’,
make sure to utilize appropriate warning notices
to minimize the potential for injury or equipment
damage.
FU2-21: Restart After Fault Reset
If FU2-21 is set to ā€˜No’, restart the inverter by
cycling the FX or RX terminal to CM terminal after
the fault has been reset.
If FU2-21 is set to ā€˜Yes’, inverter will restart after the
RST (reset) terminal has been reset a fault. If the
motor is rotating by inertia at the time power is
restored, the inverter may trip. To avoid this trip, use
ā€˜Speed Search’ function by setting bit 2 to ā€˜xx1x’.
[Reset restart: ā€˜No’]
[Reset restart: ā€˜Yes’]
CAUTION
Particular attention must be directed to this
function as motor starts to run suddenly after the
fault is reset. Otherwise, it may result in personal
damage.
Input Power
Time
FX-CM
ON
Time
Start
Power On
Output Frequency
Time
FU2
ā–ŗ
RST restart
21 No
0 21
Factory Default: No 0
Output Frequency
Time
FX-CM
ON
Time
RST-CM
ON
Time
ON
No Effect Start
Tripped
Output Frequency
Time
FX-CM
ON
Time
RST-
ON
Time
Start
Tripped
Input Power
Time
FX-CM
ON
Time
ON
No
Start
Power On
Output Frequency
Time