Chapter 6 - Parameter Description [FU2]
6-26
[Power ON Start: āNoā]
[Power ON Start: āYesā]
Note: In case of using āPower ON Startā to āYesā,
make sure to utilize appropriate warning notices
to minimize the potential for injury or equipment
damage.
FU2-21: Restart After Fault Reset
If FU2-21 is set to āNoā, restart the inverter by
cycling the FX or RX terminal to CM terminal after
the fault has been reset.
If FU2-21 is set to āYesā, inverter will restart after the
RST (reset) terminal has been reset a fault. If the
motor is rotating by inertia at the time power is
restored, the inverter may trip. To avoid this trip, use
āSpeed Searchā function by setting bit 2 to āxx1xā.
[Reset restart: āNoā]
[Reset restart: āYesā]
CAUTION
Particular attention must be directed to this
function as motor starts to run suddenly after the
fault is reset. Otherwise, it may result in personal
damage.