Chapter 6 - Parameter Description [I/O]
6-54
I/O-96: Input Checking Time
When Multi-step speed or Multi-Accel/Decel
operation is active, inverter determines the input to be
valid after the I/O-95 [Input checking time] elapses.
I/O-97: Overheat Trip Selection
Inverter Overheat protection is activated regardless of
motor temp setting condition.
Code Bit set
3 2 1
Function On Off
Motor overheat trip
setting (tripped at
I/O-98)
1 0
-Reserved- 1 0
I/O-
97
External
temperature sensor
selection (PTC/
NTC)
1 0
Caution: Bit 2 is reserved for future use.
I/O
In CheckTime
96 1 ms
1 96
Factory Default: 1 ms 1
ON (Speed-L)
Spd 0 Spd 0 Spd 0 Spd 0 Spd 7 Spd 7 Spd 7 Spd 2
BX
RX
Output
fre
q
[
Hz
]
[Input checking time]
ON
ON (FX)
ON (Speed-H)
ON (Speed-M)
ON
Input checking time Input checking time
I/O OH Trip Sel
97 111
111 97
Factory Default: 111 111
I/O MO Trip Temp
98 110
110
98
Factory Default: 110 [°C] 110