Chapter 6 - Parameter Description [FU2]
6-35
FU2-82: Software Version
Displays the software version. This will vary
depending on software version integrated.
FU2-83, 84, 85: Last Trip Time, On-time, Run-time
Displays time elapsed after last trip occurs.
Note: it is reset automatically upon trip occurs.
Displays time after Power is turned ON.
Note: it is not reset automatically.
Displays time for inverter to be run.
Note: it is not reset automatically.
FU1-83~85 display X : XX : XX : XX : XX
(Year:Month:Day:Hour:Minute)
FU2-87: PowerSet
Used to adjust the current inverter output power
and FU1-54 [KiloWattHour].
FU2-90: Parameter Display
It is used to change the parameters to be viewed.
No
FU2-90
Set data
Description
0 Default
Displays basic parameters.
(factory default)
1 All Para Displays all parameters.
2
Diff
Para
Displays parameters set
differently from factory setting.
FU2-91: Parameter Read
FU2-92: Parameter Write
This is useful for programming multiple inverters to
have same parameter settings. The LCD keypad can
read (upload) the parameter settings from the inverter
memory and can write (download) them to other
inverters. This
function is only available with LCD
keypad.
Note: When FU2-91, 92 is used, motor parameters
such as FU2-40~46, FU2-62~63 will be initialized.
Perform Auto-tuning first before using Sensorless
mode.
Note: Perform FU2-95 [Parameter save] first
before FU2-91 [Parameter Read].
FU2
►
S/W Version
82 Ver X.X
X.X 82
Factory Default: Ver. X.X X.X
FU2
►
Para. read
91 --- No ---
Factory Default: No
FU2
►
Para. write
92 --- No ---
Factory Default: No
FU2
►
LastTripTime
83 0:00:00:00:00
00.00 83
Factory Default: 0:00:00:00:00 00.00
FU2
►
On-time
84 0:00:00:00:00
00.00 84
Factory Default: 0:00:00:00:00 00.00
FU2
►
Run-time
85 0:00:00:00:00
00.00 85
Factory Default: 0:00:00:00:00 00.00
FU2
►
Para. disp
90 Default
1 90
Factory Default: Default 1
FU2
►
PowerSet
87 100
APP ▶ Jump
code
87
Factory Default: 100% 100