EasyManuals Logo

LSIS sv-ip5a User Manual

LSIS sv-ip5a
210 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #156 background imageLoading...
Page #156 background image
Chapter 6 - Parameter Description [APP]
6-74
APP-02 , APP-80 (to use Dual PID operation)
ExtPID can be used in the following three cases; ā‘ controlling other system independently like an external PID
controller ā‘”using both PID controller in APP-02 and External PID controller ā‘¢using ExtPID output as an
Inverter target frequency.
[Dual PID block diagram for case ā‘ ]
Ext.PID Parameter
DRV-20
APP-
80
Ext. PI mode
Ext.PID
K
f
Limit
APP-88
Ext. PID High Limit
Freq.
proc PI dis
APP-90
Gain
APP-89
Ext. PID Low LImit
Freq.
I/O-20~27
Multi-function Input
Terminal Setting
(M1~M8)
Ext. PID Output
Gain
Ext. PID F Gain:
Feed Foward
Ext. PID Ref Setting
Zero
APP-93
APP-81
I/O-20~27
Multi-function Input
Terminal Setting
(M1
~
M8)
APP-83
Ext. PID Run
Zer
o
APP-82
Ext. Ref Perc
S0, S1 Mode
I/O-70,-
72
Analog Meter Output
Setting
Ext. Fbk Sel
V11
Keypad3
Ext. Ref Sel
For Connection to
External Controller
(Other System)
This illustrates controlling other system independently. Set I/O-70 or 72 [S0/S1 mode] to ā€œExt PID Outā€ and
connect external system to S0 or S1 terminal. When Ext.PID Run signal is ON at the defined terminal in I/O-
20~27, it starts output.
[Dual PID block diagram for case ā‘”]
Ext.PID Parameter
DRV-20
APP-80
Ext. PI mode
Ext.PID
K
f
Limit
APP-88
Ext. PID High LImit
Freq.
proc PI dis
APP-90
Gain
APP-89
Ext. PID Low LImit
Freq.
I/O-20~27
Multi-function Input
Terminal Setting
(M1~M8)
Ext. PID Output
Gain
Ext. PID F Gain:
Feed Foward
Ext. PID Ref Setting
Zero
APP-93
APP-81
I/O-20~27
Multi-function Input
Terminal Setting
(M1~M8)
APP-83
Ext. PID Run
Zero
APP-82
Ext. Ref Perc
S0, S1 Mode
I/O-70,-72
ģ•„ė‚ ė”œź·ø ė©”ķƒ€ 출렄 설정
Ext. Fbk Sel
V11
Keypad3
Ext. Ref Sel
PID F/B
Selection
Accel/
Decel
wTarFreq
DRV-14
Target Freq.
APP-
02
proc PI mode
PID
K
f
Limit
APP-10
PID High
LImit Freq.
proc PI dis
APP-12
Gain
APP-11
PID Low
Limit Freq.
I/O-20~27
Multi-function Input
Terminal Setting
(M1~M8)
PID Output Scale
PID F Gain: Feed Foward
PID Aux Ref Setting
Freq
APP-03
APP-04
Aux Ref Mode
APP-05 APP-06
Ext. PID
Aux Ref Sel
8
I
PID F/B
0
1
1
This illustrates dual use of PID controller (APP-02) and External PID controller. Set APP-81 [Ext. Ref Sel] to

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS sv-ip5a and is the answer not in the manual?

LSIS sv-ip5a Specifications

General IconGeneral
BrandLSIS
Modelsv-ip5a
CategoryController
LanguageEnglish

Related product manuals