Chapter 9 – RS485 Communication
9-8
9.5 Parameter code list
<Common area>: Area accessible regardless of inverter models (Note 3)
Address Parameter Unit Unit R/W Data value
0x0000 Inverter model R
9 : SV-iP5A
4: 5.5kW(7.5HP), 5: 7.5kW(10HP),
6: 11kW(15HP), 7: 15kW(20HP),
8: 18.5kW(25HP), 9: 22kW(30HP),
A: 30kW(40HP), B: 37kW(50HP),
C: 45kW(60HP), D: 55kW(75HP),
E: 75kW(100HP) F: 90kW(125HP)
10: 110kW(150HP) 11: 132kW(200HP)
12: 160kW(250HP) 13: 220kW(300HP)
14: 280kW(350HP) 15: 315kW(400HP)
0x0001
Inverter capacity
R
16: 375kW(500HP) 17: 450kW(600HP)
0 : 220V Class
0x0002
Inverter Input Voltage
R
1 : 400V Class
(Ex) 0x0100 : Version 1.00
0x0003
S/W Version
R
0x0101 : Version 1.10
0x0005 Frequency Reference 0.01 Hz R/W
BIT 0: Stop (S)
BIT 1: Forward run (F)
BIT 2: Reverse run (R)
BIT 3: Fault reset (0->1)
BIT 4: Emergency stop
R/W
BIT 5: Not used
BIT 6, BIT 7: Run/Stop command source
0(Terminal), 1(Keypad), 2(Option) 3: Int. 485
BIT 8 ~12: Freq. reference
0 ~ 16: Multi-step speed freq. (0, 2~16)
17 ~ 19: UpDown (Up, Down, UD Zero)
20 ~ 21: RESERVED
22 ~ 25: Analog (V1, V1S, I, V1I)
26: Pulse 27: Sub 28: Int. 485
29: Option, 30: Jog, 31 : PID
0x0006 Run Command (Note 1)
R
BIT 15: set when Network error
0x0007 Acceleration Time 0.1 sec R/W
0x0008 Deceleration Time 0.1 sec R/W
0x0009 Output Current 0.1 A R
0x000A Output Frequency 0.01 Hz R
0x000B Output Voltage 0.1 V R
0x000C DC Link voltage 0.1 V R
0x000D Output power 0.1 kW R
BIT 0: Stop
BIT 1: Forward running
BIT 2: Reverse running
BIT 3: Fault (Trip)
BIT 4: Accelerating
BIT 5: Decelerating
0x000E Operating status of Inverter
R
BIT 6: speed arrival