4. Parameters
4-16
(3) Input signal logic definition
XDL-L7 Drive allows for defining the logic of input signals for 10 hardware contacts from DI1
to DIA through parameters [P2-08] and [P2-09].
The logic of input signals as set in the factory is as follows.
Signal Name Input
Signal
(Initial
name)
CN1 Pin Default Allocation Number
Contact B
Input
signal
logic
setting
Default
setting
Parameter
Allocation
48 18 19 20 46 17 21 22 23 47
Servo ON
[P2-08].Set Digit 1
SVON
1 0
[P2-08] 0x11111
Multi-speed 1
[P2-08]. Set Digit 2
SPD1
1 0
Multi-speed 2
[P2-08]. Set Digit 3
SPD2
1 0
Multi-speed 3
[P2-08]. Set Digit 4
SPD3
1 0
Alarm reset
[P2-08]. Set Digit 5
ALMRST
1 0
Select rotation
direction
[P2-09]. Set Digit 1
DIR 1 0
[P2-09] 0x10001
Forward rotation
prohibited
[P2-09]. Set Digit 2
CCWLIM 0
Reverse rotation
prohibited
[P2-09]. Set Digit 3
CWLIM 0
Emergency stop
[P2-09]. Set Digit 4
EMG
0
Stop
[P2-09]. Set Digit 5
STOP
1 0
NOTE 1) For the purpose of the input signal logic definitions, Contact A is 1 and Contact B is 0.
Input signal logic definition
Input signal logic definition number