9.5 Reset
Reset operation resets the active applications and initializes the variables.
Reset is divided into the following four types and variables that are initialized dif
fer according to
the reset type.
Reset Warm
Initializes variables other than the RETAIN and PERSISTENT variables.
Reset Cold
Initializes variables other than the PERSISTENT variable.
Reset Origin
Initializes all variables. Active applications are deleted from the GM1 controller.
Device Reset
Initializes all variables and device user management information. Applications and source
code are deleted from the GM1 controller.
● The following table shows the items that are initialized by each reset operation.
〇: Retained
×: Initialized
Update: Updated
Operatio
n
Variable
s other
than
"RET
AIN
/
PERSIS
TENT"
RETAIN
variable
(RETAIN
)
PERSIS
TENT
Variable
s
(PERSIS
TENT)
Applicati
on
User
manage
ment
Boot
applicati
on
Source
file
IP
address
RTC
time
zone
Stop 〇 〇 〇 〇 〇 〇 〇 〇 〇
Reset
warm
× 〇 〇 〇 〇 〇 〇 〇 〇
Reset
Cold
× × 〇 〇 〇 〇 〇 〇 〇
Downloa
d
× × 〇 Update 〇 Update Update Update 〇
Online
change
〇 〇 〇 Update 〇 Update Update 〇 〇
Power
cycling
× 〇 〇 〇 〇 〇 〇 〇 〇
Reset
Origin
× × × × 〇 〇 〇 〇 〇
Resetting
"Device
"
× × × × × × × 〇 〇
Resetting
"Device
"
by
means of
hard
switching
× × × × × × × 〇 〇
9.5 Reset
9-18 WUME-GM1RTXOP-01