1. T
urn the controller OFF and then ON.
If the problem persists, consult your Panasonic representative.
9.9.5 Error Code List
Error
No.
Operatio
n
Name Error description and action method Recover
y
method
0x0001 Stop System error
(serious)
Notify us of the error information or system data history
information displayed on the status window of GM
Programmer
.
Power
cycle
0x0002 Stop System error
(CODESYS)
Notify us of the error information or system data history
information displayed on the status window of GM
Programmer
.
Power
cycle
0x0003 Continue System error
(minor)
Notify us of the error information or system data history
information displayed on the status window of GM
Programmer
.
Power
cycle
0x0106 Continue Device date
and time, R
TC
error
Because the duration of the power failure exceeded the
guaranteed period (14 days), the RTC time information was
initialized.
The device must be left ON for at least 10 minutes. (Time
information is reset to April 1, 2019.)
Clear the
error
0x0110
to 0x113
Continue PWM
Frequency
setting error
The cycle setting is out of range. Check whether the duty
ratio is within the allowable range.
Re-
downloa
d
0x0120
to 0x123
Continue PWM
Duty ratio
setting error
The duty ratio setting is out of range. Check whether the
duty ratio is within the allowable range.
Re-
downloa
d
0x0130
to 0x131
Stop Counter
Overflow error
The counter value exceeds the upper limit. Perform reset or
preset operation so that the counter value falls within the
range between the upper and lower limits.
Re-
downloa
d
0x0140
to 0x141
Stop Counter
Underflow
error
The counter value drops below the lower limit. Perform reset
or preset operation so that the counter value falls within the
range between the upper and lower limits.
Re-
downloa
d
0x0150
to 0x151
Continue Counter
Reset
abnormal error
The count value becomes 0 under the reset conditions and
goes out of the range between the upper and lower limits.
Check the settings of the upper and lower limits of the
counter
. If 0 does not exist in the range between the upper
and lower limits, make a preset request.
Re-
downloa
d
0x0160
to 0x161
Continue Counter
Preset
abnormal error
The count value goes out of the range between the upper
and lower limits under the preset conditions. Check whether
the preset value falls within the range between the upper
and lower limits.
Re-
downloa
d
0x0170
to 0x171
Continue Counter
Current value
change
abnormal error
The count value goes out of the range between the upper
and lower limits when the current value is changed. After the
current value is changed, check whether the new value falls
within the range between the upper and lower limits.
Re-
downloa
d
0x0200 Continue Expansion unit An expansion unit communication error has occurred. Check
connections.
Clear the
error