8.8.4 Online Change
Online change allows the user to change applications without having to stop the GM1 controller
during operation. Executing online change downloads only dif
ferent applications to the GM1
controller.
If the applications generated by build during login differ from the applications within the GM1
controller, the following dialog box will be displayed.
Login with online change
Executes login by downloading only dif
ferent applications without stopping the GM1 controller
Login with download
Executes login by downloading applications generated by build with the GM1 controller
stopped
Login without any change
Executes login without downloading the applications generated by build
Do not clear the "Update bootproject" check box. If you clear the check box, the applications
will not be saved when the GM1 controller is turned OFF
.
8.8.5 Code Analysis (Static Analysis Light)
Code analysis (Static Analysis Light) can be conducted on programs that are created.
Code analysis can check for the following errors.
Error number Description
SA0033 Unused variables
SA0028 Overlapping memory areas
SA0006 Write access from several tasks
SA0004 Multiple write accesses on output
SA0027 Multiple uses of identifiers
SA0167 Report of temporary function block instance