2. Select "Modbus TCP Master
" under "Modbus" and click the [Add Device] button.
"Modbus_TCP_Master" will be added to the "LANPort1" object.
Example: When master communication is performed via LAN port1
3. Right-click the
"Modbus_TCP_Master" object in the navigator pane and then select Add
Device from the context-sensitive menu that is displayed.
The "Add Device" dialog box will be displayed.
4. Select "Modbus TCP Slave
" under "Modbus TCP Slave" and click the [Add Device] button.
"Modbus_TCP_Slave" will be added to the "Modbus_TCP_Master" object.
Example: When master communication is performed via LAN port1
5. Open the device (AGM1CSR16T1) of the GM1 controller
, select the "'PLC' Parameters" tab,
and set the IP address of LAN port1.
13.3 MODBUS