(2) For the following items, the settings cannot be changed.
Install to Device Repository
The remote adapter device specified here is registered as a device in CODESYS.
Export EDS File
The EDS file specified here is output.
For scanner device settings, use the EDS file provided by Panasonic
("PanasonicGM1CSRX16_0005_0101.eds").
Setting up a module device
Set up a module device, as below.
1. Double-click
"EtherNet_IP_Module" in the navigator pane.
2. In the "General" tab, set module information.
2-1 (1) Select a desired module type from the following 10 types.
Module type Size Direction
Byte Input 1 byte O→T
Byte Output 1 byte T→O
Word Input 1 word (2 bytes) O→T
Word Output 1 word (2 bytes) T→O
DWord Input 1 double-word (4 bytes) O→T
DWord Output 1 double-word (4 bytes) T→O
Real Input 1 single-precision real number (4 bytes) O→T
Real Output 1 single-precision real number (4 bytes) T→O
13.4 EtherNet/IP
13-54 WUME-GM1RTXOP-01