40. OPTIONAL EXTENSIONS MODULES
40.1. Additional I/O module
The module has been designed to improve functionality of an indicator
for additional 12 inputs and 12 outputs. The module features optoisolated
inputs and solid-state relay outputs. It enables free inputs and outputs setup
(using indicator menu). Module’s housing cover features two cable glands
through which cables are fed, which cables are 3-metre long and terminated
with stripped wires.
Caution:
Installed 12IN/12OUT module disables installation of ANxxxx analog output
module.
40.1.1. 12IN/12OUT module: technical specifications
Output parameters
Outputs number 12
Outputs types Solid-state relay
Wire cross-section 0,14 - 0,5mm
Maximum switching current 0,5A DC
Maximum forward voltage 30VDC, AC
Input parameters
Input number 12
Input types Optoisolated
Wire cross-section 0,14 – 0,5mm
Control voltage 5 -24V DC